KSO-6 (10) kV chambers with aerial insulation, gas-insulated disconnector and vacuum circuit breaker
KSO chambers forms the system of modular chambers with aerial insulation of cable and busbar cells, gas-insulated load-break switches, grounding switches with aerial insulation, vacuum circuit breakers, measuring voltage and current transformers, control, protective and measuring devices. The different combinations of devices correspond to different versions.
The chambers are designed for switchgears at the rated voltage 6 or 10 kV of the three-phase alternating current with the frequency of 50 or 60 Hz of systems with the insulated neutral or grounded through the arcing ground suppressor or resistor.
The chambers can be used as bushing devices in complete transformer substations 6(10)/0.4 kV.
Due to reduced overall dimensions they can be installed in any compact, mobile or underground switchgears and substations. Modular design makes KSO chambers the ideal solution for updating and extension of the existent substations and switchgears.
1.3 Standards compliance
KSO-6 (10) chambers meets the requirements of:
-GOST 12.007.0-75, GOST 12.007.4-75, GOST 1516.3-96, that is proved by conformance certificate № РОСС.RU.АИ18.В08563;
-technical conditions ТU 3414-008-00109458-2005
- Regulations of electric units arrangement (PUE)
2. TECHNICAL FEATURES
2.1 Basic parameters, overall dimensions and weight of KSO chambers
Parameter designation |
Dimension | |||
Rated voltage, kV |
6.0 |
10.0 | ||
Maximum operation voltage, kV |
7.2 |
12.0 | ||
Main circuits’ rated current, A |
400;630 | |||
Busbars’ rated current |
630;800;1000 | |||
Peak withstand current, kA |
51 | |||
Short-time withstand current during 1 s, kA |
20 | |||
Rated current of tripping of vacuum circuit breakers, kA |
16;20 | |||
Testing voltage of composite lightning impulse, kV |
60 |
75 | ||
Rated current of safety fuses, A |
6.3; 10; 16; 25; 31.5; 40; 50; 63; 80; 100; 125; 160; 200 | |||
Rated current of cutout fuse of power fuses, kA |
6.3 , 160 A |
63 | ||
200 A |
50 | |||
Rated current of current transformers, A |
50; 75; 100; 150; 200*; 300; 400; 600 | |||
Rated voltage of secondary circuits, V |
direct current |
24; 110; 220 | ||
alt.current |
220 | |||
lighting (a.c.) |
220 |
| ||
Type of covers and protection degree acc. to GOST 14254 |
IP31 | |||
Overall dimensions, mm |
width |
375, 500, 600, 750 | ||
depth |
900, 1250 | |||
height |
without BRZ |
1670 | ||
with BRZ |
1870 | |||
Chamber weight max, kg |
340 |
(*) The values of peak withstand current and short-time withstand current of the chamber are determined by the value of peak withstand current and short-time withstand current of the current transformers. The values of 51 kA and 20 kA correspond to the current transformers with rated current of 200 A and more.
2.2 KSO chambers execution
Name of grading factor |
Execution |
KSO chambers type depending on switching devices type |
In compliance with main circuits schemes |
Busbar system |
With one busbar system |
The way of phase separation |
With unseparated phases |
Insulation level acc. to GOST 1516.3 |
with normal insulation |
Busbars insulation |
with insulated busbars with uninsulated busbars |
Connection design |
With cable connection With bus connection |
Kind of installation |
For indoor installation |
Environmental protection type |
Without special protection |
Service conditions |
Of single-sided service |
Rated dimensions of climatic parameters – according to GOST 15150, GOST 15543.1:
ambient air temperature – from 0 0C till +40 0C for U3, UHL3;
ambient air temperature – from 0 0C till +35 0C for UHL4;
ambient air temperature – from 0 0C till +45 0C for T3;
altitude level above sea max – 1000 m (over 1000 m – special execution);
the environment is not explosive, without current-conducting dust, aggressive evaporation and gases, that can be harmful for metal and insulation.
relative humidity – not more than 80% at +20 0C.
Note. If the mounting of KSO chambers in the place with ambient air temperature under 0 0C is necessary, then installation of heating elements (thermostats) must be provided to ensure the normal temperature conditions of the equipment operation. Mechanical strength of KSO chambers in the sense of influence of mechanic environmental factors must be correspond to M6 group of service conditions according to GOST 17516.1. Normally KSO chambers are of continuous running duty. Insulation resistance and electric strength of main and auxiliary circuits meet the following requirements:
Name of the circuits |
Insulation resistance, megaohm, no less than |
Testing voltage, kV |
Test duration, min |
secondary circuits (without lighting) |
1 |
2 |
1 |
6-kV circuits (without dischargers) |
1000 |
32 |
1 |
10-kV circuits (without dischargers) |
1000 |
42 |
1 |
3 TECHNICAL DESCRIPTION
List of KSO chambers types is given in the table below.
№ |
Chamber type |
Chamber function |
|
DS-TA |
chamber of lead-in, outgoing lines |
|
DS-SA |
sectional chamber |
|
RM-F |
measuring chamber with voltage transformer |
|
SF |
chamber of outgoing lines with load-break switch and safety fuse, transformer protection |
|
LS |
chamber of load-break switch and grounding switch |
|
L |
chamber with load-break switch of lead-in and outgoing lines |
|
LT |
chamber with grounding switch of cable lead-in and outgoing lines |
|
R |
chamber of cable lead-in and outgoing lines |
|
TF1 |
chamber of transformer 25-40 kVA |